Slant Fin Corp. Controller and Display CHS Series
10
2.4.1 CH Config
Figure 2-8 Central Heat Configuration Main Menu Screen
CH Config main menu screen, accessed by
selecting “CH Config” from the “Advanced Setup”
screen, lists the sub-menus specific to the Central Heat
Configuration. Use the up and down (▲▼) buttons to
navigate the menu options; when the desired option is
highlighted select by pressing the “OK” button.
The settings under “CH Config” are specific to boiler
operation given a local central heat demand, i.e. CH1
heat input.
2.4.1.1 CH Config CH Config
Figure 2-9 Central Heat Configuration Sub-menu Screen
CH Config sub-menu screen, allows the installer to
set parameters specific to the boiler response and
operation for local (i.e. non Lead Lag) Central Heat
demands. Use the up and down (▲▼) buttons to
navigate the menu options; when the desired option is
highlighted select by pressing the “OK” button.
Demand switch - Central heat demand can be
initiated by a contact closure to CH1, “LCI”, or by
boiler temperature, “Sensor only”.
Setpoint source The boiler setpoint can be “Local”,
i.e. the “CH setpoint” set from the display, or “4-
20mA” set from an external source.
Modulation sensor With the “Setpoint source” set
to “Local”, the control can be set to use either the
“Outlet”, “Inlet” or “S10(pipe) sensor for regulation
of burner modulation.
Mod rate source The burner modulation can either
be controlled by the boiler control, “Local”, or by an
external source, “4-20mA”.
Demand switch
Setpoint source
CH setpoint
Off hystersis
On hysteresis
Modulation sensor
Mod rate source
CH Config
LCI
Local
180
o
F
10
o
F
20
o
F
Outlet
Local
CH Config
Outdoor Reset Config
Warm weather shutdown
CH Config