MODEL 3000
220°F (104°C) Max High Limit
MODEL 3000-190
190°F (88°C) Max High Limit
High Temp Limit / LWCO Control
with Thermal Targeting
for Gas Water Boilers
24 VAC Operating Voltage
PATENT NO. 7,891,572
Three
Function
Design
Temperature Limit Control
Provides high limit functionality for
cold start boilers.
Low Water Cut-Off
Provides protection against potentially
dangerous low water conditions
when installed with the Hydrolevel
Electro-Well™ (see page 2 for details).
Boiler Reset Control
Utilizes
Thermal Targeting
technology to conserve fuel by
monitoring heating demand and
establishing target boiler temperatures
below the high limit setting
(see page 5 for details).
INSTALLATION INSTRUCTIONS
and OPERATING MANUAL
• Saves Fuel Features Thermal Targeting™ technology and
Thermal Pre-Purge capability
• Universal Design Replaces common High Temp Aquastats*
• Easy to Install Industry standard wiring, dial-type settings,
no external sensors necessary
• Operating Indicators LEDs and Test Button provide continual and
on-demand status checks
• Prioritizes Hot Water Gives priority to calls from indirect water heater
*Aquastat is a registered trademark of Honeywell International, Inc.
WARNING
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
CAUTION
To prevent serious
burns, boiler
should be thoroughly cooled before installing or
servicing control.
WARNING
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
Model 3000
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Function

183 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comMODEL 3000220°F (104°C) Max High LimitMODEL 300

Page 2

2MOUNTING THE CONTROLSTEP 1Insert sensor ALL THE WAY into well. (Fig. 1)STEP 2 Place control on the well.While holding box against well nut,tighten we

Page 3 - Step  Step 

3WARNINGElectrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing this c

Page 4 - #45-531-56

4WARNINGElectrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing this c

Page 5 - Differentials

Setting the High Limit The high limit is factory set at 190°F. To adjust, turn the HI TEMP Dial to the desired setting. Setting range: Model 3000 – 1

Page 6 - Model 3000 shown above

6 HI TEMP Illuminates when theboiler water temperature reaches thehigh limit setting. It will remain lit untilthe water temperature falls 10° (seeHig

Page 7

Yes왘 Recheck WiringIs theLimit CircuitClosed?YESDoes the Control HavePower?NO7NONOIs theRed LED(LOW WATER)On?The Control isSensingLow Water.CAUTION –

Page 8 - SPECIFICATIONS

883 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comSPECIFICATIONSFUEL SMART HYDROSTAT MODEL 3000 a