Slant_fin 3200-Plus User Manual

Browse online or download User Manual for Equipment Slant_fin 3200-Plus. Slant/Fin 3200-Plus User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
1
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 FAX (203) 773-1019 www.hydrolevel.com
MODEL 3200-Plu s
Temp Limit / LWCO Control
with Thermal Targeting
for Water Boilers
120 VAC Input / 24 VAC Burner Circuit
PATENT NO. 7,891,572
WARNING
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
CAUTION
To prevent serious
burns, boiler
should be thoroughly cooled before installing or
servicing control.
WARNING
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
Three Function
Design
Temperature Limit Control
Designed for cold start and tankless
coil boilers.
Low Water Cut-Off
Provides protection against potentially
dangerous low water conditions
when installed with the Hydrolevel
Electro-Well™ (see page 2 for details).
Boiler Reset Control
Thermal Targeting On-board micro-
processor adjusts boiler temperature
based on heating demand.
Outdoor Reset Ready Compatible with
Hydrolevel OS-100 Outdoor Sensor Kit
(sold separately) for outdoor reset and
warm weather shut-down functionality.
INSTALLATION INSTRUCTIONS
and OPERATING MANUAL
• Saves Fuel Features Thermal Targeting™ technology and
Thermal Pre-Purge capability
• Outdoor Reset Ready – Provides Outdoor Reset and Warm Weather
Shut-Down capability with the addition of Hydrolevel OS-100 Outdoor
Sensor Kit (sold separately)
• Universal Design Replaces common cold-start and triple-action
Aquastats*
• Operating Indicators LEDs, Dynamic Display and Test Button provide
continual and on-demand status checks
• Prioritizes Domestic Hot Water – Gives priority to low limit setting or to
calls from indirect water heater
• Reduces Condensation Holds circulator off until boiler reaches 125°F
*Aquastat is a registered trademark of Honeywell International, Inc.
HydroStat 3200-Plus Instructions Page 1
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - Three Function

183 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comMODEL 3200-Plu sTemp Limit / LWCO Controlwith T

Page 2 - Installing HydroStat

10Restore Factory Default SettingsTo restore all features to the factory default settings (see following chart for default settings)1. Turn the LO TEM

Page 3 - Part No. Description

11 TEMP ACTIVE Indicates that the Fuel SmartHydroStat control is powered and that the temperaturefunction is active. TEMP HI TEMP Illuminates when t

Page 4

12MAINTENANCERemove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts thatare exposed

Page 5 - ZONE VALVE WIRING

13NOYESNOIs theThermostat (T/TV) Calling for Heat?Is There24 VACBetween B1and B2?NOIs the Indirect (I1-I2) Calling for Heat?NOIs theLow Limit Dial Set

Page 6 - Setting the Economy Feature

14YESRecheckWiring.ReplaceControl.When there is no call to fire the burner, the voltageshould be 0 volts between B1 and B2. Make sure the burner is w

Page 7

15ELECTRO-WELLSFuel Smart HydroStatinstalled with Electro-Well™When installed with the Hydrolevel Electro-Well, FuelSmart HydroStat will provide both

Page 8 - Thermal Pre-Purge

1683 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.comOUTDOOR SENSOR KITHydrolevel's optional O

Page 9 - Low Water Cut-Off Function

2IMMERSION WELLSWhen installed on an Electro-Well™ (sold separately), the LowWater Cut-Off function is automatically activated. Heat transfergrease sh

Page 10 - OPTIONAL FEATURES continued

MOUNTING THE CONTROLSTEP 1 Two mounting positions are available on the back of the control (Fig. 1). Select which of the two positions (2 knockouts)

Page 11

4WIRINGWARNINGElectrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing

Page 12 - TROUBLESHOOTING

5WIRING continuedWARNINGElectrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or

Page 13

NOTE: Settings can be checked using the TEST/SETTINGS Button. See page 11 for details.Setting the High Limit The high limit is factory set at 190°F. T

Page 14 - WARNING!

7HOW THERMAL TARGETING WORKSSYSTEM START-UPRECORD YOUR SETTINGSThermal Targeting technology analyzes thermostat activity and continually evaluates how

Page 15 - Electro-Well™ Models

8OPTIONAL FEATURESNOTE: The Program Mode ––is accessed by turning the LO TEMP dial to a position just above OFF.Thermal Pre-PurgeThermal Pre-Purge is

Page 16 - SPECIFICATIONS

9OPTIONAL FEATURES continuedCirculator Activation OptionsWhen in the default mode, the HydroStat activates the circulator (C1/C2 contacts) on calls to

Comments to this Manuals

No comments