INSTALLATION AND OPERATING INSTRUCTIONS
SC-9 Controller
M
ODULAR BOILER CONTROLLER SERIES
SC-9 Applications
Space heat systems with outdoor reset
Constant temperature setpoint control
Any of these in combination with domestic
hot water heating
If your system is different than the above, call the Slant/Fin
technical services group at 800-873-4346 to
determine if the control can accommodate it.
Controller Packing List
1- SC-9 Modular controller P/N 435081
1- Outdoor sensor with enclosure P/N 339070
2- Universal sensors P/N 339071
1- Used as supply water sensor
1- Used as return water sensor
The SC-9 is a microprocessor control which will sequence up to
nine heating stages based on outdoor air temperature and supply
water temperature. Designed to handle a Caravan gas-fired,
oil-fired or dual fuel-fired hot water heating plant for space heating
or “Setpoint” operation, or either in combination with domestic
water heating. A large easy to read display provides current
system temperatures and operating status. The control has outputs
for a primary pump and either a combustion air damper or alarm.
ADDITIONAL FUNCTIONS INCLUDE:
Primary pump output. Pump exercising. Pump purging. Boiler
demand for space heating loads. Set point demands for set point
loads. Test sequence to ensure proper component operation. CSA
C US certified. Setback input for energy savings.
SPACE HEATING OPERATION: When the outdoor air tempera-
ture drops below a preset value, the heating system is energized.
The SC-9 Controller determines the number of stages required to
meet the space heating needs and fires them. During operation,
the Controller scans system temperatures, adding or deleting
stages as necessary to satisfy heating load.
CONTENTS
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
a) Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
b) Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
c) View of Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
d) System Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Select System Type . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
A. Space heating only with outdoor reset . . . . . . . .13
a) Dip switch settings . . . . . . . . . . . . . . . . . . . . . . .13
b) Functions and defaults . . . . . . . . . . . . . . . . . . . .15
c) Adjusting the settings . . . . . . . . . . . . . . . . . . . . .15
B. Space heating only w/setpoint control . . . . . . . . .18
a) Dip switch settings . . . . . . . . . . . . . . . . . . . . . . . . .18
b) Functions and defaults . . . . . . . . . . . . . . . . . . . . . .18
c) Adjusting the settings . . . . . . . . . . . . . . . . . . . . . . .18
C. Space heating w/DHW w/outdoor reset . . . . . . . .19
a) Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . .19
D. Space heating w/DHW w/setpoint control . . . . . . .20
a) Dip switch settings . . . . . . . . . . . . . . . . . . . . . . . . .20
b) Functions and defaults . . . . . . . . . . . . . . . . . . . . . .21
c) Adjusting the settings . . . . . . . . . . . . . . . . . . . . . . .21
Detailed Information for Adv Mode of
Adv / Installer Dip Switch . . . . . . . . . . . . . . . . . . . . . . . . .22
Viewing the Performance . . . . . . . . . . . . . . . . . . . . . . . . .27
Useful Hints and Reloading Factory Defaults . . . . . . . .28
Testing the control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Factory Default Listings . . . . . . . . . . . . . . . . . . . . . . . . . .32
SETPOINT OPERATION:
The SC-9 adds and deletes stages to minimize the difference
between the desired Setpoint temperature and the actual meas-
ured Supply Water Temperature.
DOMESTIC WATER HEATING:
When configured for “DHW” (Service Water Heating), the control
holds stage #9 out of the Lead/Lag firing sequencing until all other
active stages are energized. Only when the heating load reaches
a maximum will the Stage #9 relay energize. At the same time, a
motorized valve opens allowing the DHW modules to contribute to
space heating. If water temperature in the DHW modules falls
below a pre-set value, the motorized valve will close, retaining
module capacity for domestic water heating.
Printed in U.S.A. 1206 PUBLICATION SC9-40
Part No. 435083000
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - SC-9 Controller

INSTALLATION AND OPERATING INSTRUCTIONSSC-9 ControllerMODULAR BOILER CONTROLLER SERIESSC-9 Applications• Space heat systems with outdoor reset• Consta

Page 3

SC-9 Controller 11Symbol DescriptionStageDisplays which stage relays are turned on.Primary PumpDisplays when the primary pump relay is turned on.Combu

Page 4 -  ˚F ˚C  ˚F ˚C  ˚F ˚C 

12User InterfaceThe control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor

Page 5 - SC-9 Controller 5

SC-9 Controller 13GeneralThe DIP switch settings on the control are very important and should be set to the appropriate settings prior to making any a

Page 6 - WIRING THE SYSTEM

14SPACE HEATING ONLY WITH OUTDOOR RESETRotate / OffThe Rotate / Off DIP switch selects whether or not the control is to provide Equal Run Time Rotatio

Page 7 - SC-9 Controller 7

THE CONTROL MUST BE ADJUSTED FOR YOUR APPLICATION. IF ANY OF THE DEFAULT SETTINGS DO NOT SUIT YOUR APPLICATION, GO TO THE ADJUSTING SECTION THAT FOLLO

Page 8

16Boiler 2 - Selects whether or not module 2 is operational - Au (auto) or OFFDO NOT CHANGEPress the Menu button until ADJUST is visible on the top li

Page 9 - SC-9 Controller 9

SC-9 Controller 17Boiler Mass - This inputs the thermal mass characteristics of the boiler modules.Press the Menu button until ADJUST is visible on th

Page 10

18B. SPACE HEATING ONLY WITH SETPOINT CONTROLSTEP 1: With the exception of Adv / Installer DIP switch, all DIP switches should be set the same as in S

Page 11 - DISPLAY:

SC-9 Controller 19C. SPACE HEATING WITH DHW WITH OUTDOOR RESETGeneralThe DIP switch settings on the control are very important and should be set to th

Page 12 - SELECT SYSTEM TYPE:

2Remove the safety dividersfrom the wiring chamber bypulling them straight out of theirgrooves.The control can be mounted ona standard DIN rail. First

Page 13 - Set to Installer

20D. SPACE HEATING WITH DHW WITH SETPOINT CONTROLGeneralThe DIP switch settings on the control are very important and should be set to the appropriate

Page 14 - Off / Exercise

DisplayDescriptionDefault SettingNewSettingSC-9 Controller 21STEP 2: Program the following steps.XOutdoor Design - For Setpoint Operation MUST be adju

Page 15 - (18.5˚C)

22Detailed information for ADV mode of ADV / Installer DIP switchThe SC-9 control has many features and some of these features are rarely used. These

Page 16 - Default

SC-9 Controller 23Boiler 1 - Selects whether or not boiler 1 is operationalThis item is available in all modes.Range Available: Au (Auto), OFFAuBoiler

Page 17 - (93.5˚C)

24Outdoor Design - The design outdoor air temperature used in the heat loss calculations for the heating system.This item is only available if the Ext

Page 18

SC-9 Controller 25Stage Delay - The minimum time delay between the operation of stages.Range Available: Au (Auto), 0:30 to 19:55 min (5 second increme

Page 19 - ONTROL SET UP

26Primary Pump Purge - The maximum length of time that the primary pump will continue to operate after the boiler demand has been removed.Range Availa

Page 20 - Must be set to fix last

SC-9 Controller 27VIEW THE PERFORMANCEFUNCTION DESCRIPTION STEPSOUTDOORCurrent outdoor air temperature as measured by the outdoor sensor.Press the Men

Page 21

USEFUL HINTS28Hint #1Reloading Factory DefaultsTo reload the factory defaults, power down the control for 10 seconds. Power up the control while simul

Page 22

SC-9 Controller 29TESTING THE CONTROLThe control has a built-in test routine that is used to test the main control functions. The control continually

Page 23

MOUNTING THE SENSORNote: The temperature sensor (thermistor) is built into the enclosure.• Remove the screw and pull the front cover off the sensor

Page 24

30Error MessagesThe control was unable to read a piece of information stored in its memory. Because of this, thecontrol was required to reload the fac

Page 25 - (15.5˚C)

SC-9 Controller 31Technical DataControl –– Microprocessor PID control; This is not a safety (limit) control.Packaged weight –– 3.3 lb. (1500g), Enclos

Page 26

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin

Page 27 - VIEW THE PERFORMANCE

4WIRING AND TESTING THE SENSORWARNING: Do not run sensor wires close to and parallel to telephone or power cables. If the sensor wires are located in

Page 28 - USEFUL HINTS

SC-9 Controller 5

Page 29 - TESTING THE CONTROL

WIRING THE SYSTEMUse one of the following wiring diagrams to wire your system, along with the appropriate diagram on page 10.1. Gas fired - space heat

Page 30 - Error Messages

SC-9 Controller 72. Gas fired - space heating with DHWNOTE: For boiler termination wiring at modules, see page 10

Page 31 - Technical Data

83. Oil fired - space heating onlyNOTE: For boiler termination wiring at modules, see page 10

Page 32 - Request Pub. No. SC9-40 (pdf)

SC-9 Controller 94. Oil fired - space heating with DHWNOTE: For boiler termination wiring at modules, see page 10

Comments to this Manuals

No comments